Introducing MICA®: Rapid Legionella Testing
- By: Dr. Abe Cullom
- Tags: Legionella
When Legionella is a concern, facility teams usually face a trade-off. They can get fast answers that don’t show whether the bacteria are still alive, or they can wait more than a week for culture results. MICA testing can help close that gap. In this post, we introduce MICA, explain how it works, and discuss where MICA fits in a comprehensive water management program.
What is MICA Legionella Testing?
MICA is a culture-based method for detecting and counting Legionella pneumophila—the species responsible for most cases of Legionnaires’ disease—in water samples and swabs. Like conventional culture, MICA measures culturable bacteria: live cells that can grow under laboratory conditions. Unlike conventional culture methods, MICA doesn’t require L. pneumophila colonies to grow large enough to count by eye.
That difference shows up in turnaround. Pace® expects to provide MICA results in approximately three business days, compared with 7 to 10 days for traditional culture, subject to sample receipt, scheduling, and project-specific laboratory requirements. Results are reported in CFU/mL, the same units used for culture-based action levels, so they fit the way most teams already evaluate their data. As always, we will provide results via our client portal so you have them as soon as we report them.
How MICA Legionella Testing Works
MICA pairs a specialized labeling chemistry with automated imaging and artificial intelligence. After membrane filtration, the sample is incubated on selective culture media for about 48 hours. During that time, live L. pneumophila absorbs a modified sugar that makes its microcolonies glow under a fluorescent tag—long before they’re visible to the naked eye.
The MICA instrument then scans each sample, allowing AI trained to recognize L. pneumophila to identify and count colonies by size, shape, and fluorescence. The result is a consistent, objective count, without manual plate reading.
Download our white paper, Rapid Detection of L. pneumophila with MICA® Advance, for more technical details on MICA testing for Legionella.
Why Viability Matters When Testing for Legionella
While MICA offers tremendous speed advantages, choosing a Legionella test method often starts with one question: do you need to know whether Legionella is present, or whether live Legionella is present? For most water management decisions, the second question is the one that matters.
Only live bacteria can multiply in a water system and cause Legionnaires’ disease. After disinfection, DNA from dead cells can linger in the system, so a test that can’t tell living cells from dead ones may keep reporting positives after the treatment has worked. That can keep cooling towers, fountains, and other equipment offline longer than necessary
How MICA Compares to Other Legionella Test Methods
MICA | Conventional culture | Legiolert® | qPCR | Viability qPCR | |
|---|---|---|---|---|---|
What it measures | Live, culturable cells | Live, culturable cells | Live, culturable cells | DNA from live and dead cells | DNA from cells with intact membranes |
Species detected | L. pneumophila (all serogroups) | All culturable Legionella species | L. pneumophila (all serogroups) | Depends on assay | Depends on assay |
Serogroup identification | No | Yes | Isolates can be serotyped | Limited, assay-dependent | Limited, assay-dependent |
Typical turnaround | ~3 business days | 7-10 business days | 7 days incubation | 1-2 days | 1-2 days |
Units reported | CFU/mL | CFU/mL | MPN (CFU equivalent) | Genomic uniuts (GU) | Genomic units (GU) |
Comparable to CFU action levels | Yes | Yes | Yes | No | No |
Handles high background bacteria | Well suited | Can be overgrown | — | Not affected | Not affected |
Turnaround times are typical and depend on sample receipt, scheduling, and project requirements.
Where MICA fits in a Water Management Program
MICA Legionella testing can support every stage of water management, from confirming that a system is under control to responding when an outbreak is suspected.
Legionnaires’ disease investigations — When a Legionnaires’ disease case is linked to a facility, investigators need to find potential sources quickly. MICA provides fast, culture-based detection of live L. pneumophila, helping narrow down likely sources while full culture results and serogroup identification are pending.
Remediation and return to service — After a positive result, systems and equipment often stay offline until follow-up testing shows remediation was effective. With culture-based results in about three business days, MICA may be able to help bring cooling towers, hot tubs, fountains, and other equipment back online sooner. We’ll take a closer look at MICA for remediation testing in an upcoming post.
Outbreak response — During an outbreak, cautionary measures may require shutting down a wide range of suspected systems, disrupting operations, occupants, and public health protection efforts. By helping teams narrow the likely sources more quickly, MICA can support faster, evidence-based decisions. Learn more about Pace® Legionella Outbreak Response Services
Routine Legionella monitoring — Regular testing shows whether your water management program is keeping Legionella in check. Pairing MICA with scheduled culture testing gives you an early look at live L. pneumophila levels, so you can spot changes and adjust treatment sooner. This is especially useful for water treaters managing multiple sites and for facilities such as data centers, hotels, and apartment complexes that depend on uninterrupted water systems.
Frequently Asked Questions About MICA Legionella Testing
For facility teams, faster culture-based answers can be a game changer, but MICA is much newer to the market than conventional culture and PCR, which have been part of Legionella testing for decades. As always, a new method raises new questions about how it works, where it fits, and what its advantages and limitations are.
We’ve answered some of the most common MICA Legionella testing questions below. If we didn’t get to yours, contact a Pace® Legionella testing specialist.
Q: What are the limitations of MICA?
MICA is a validated, culture-based method, but it’s designed for specific testing needs and doesn’t replace standard culture in every situation. Key limitations include:
It’s specific to L. pneumophila. MICA detects Legionella pneumophila across all serogroups, the species responsible for most cases of Legionnaires’ disease, but it doesn’t detect other Legionella species.
It doesn’t identify serogroups or provide isolates. MICA reports a total count of culturable L. pneumophila in CFU/mL. When an investigation requires serogroup identification, isolates for further typing, or broader species identification, standard culture is needed.
It isn’t currently part of the CDC ELITE program or state accreditation programs. Standard culture remains the method of record for most compliance reporting, including programs that require testing by an ELAP-accredited laboratory.
It counts culturable bacteria only. Like other culture methods, MICA may not detect cells that are alive but too stressed to grow under laboratory conditions, known as viable but nonculturable (VBNC).
Q: Is MICA a validated method?
Yes. The method has been independently validated. MICA received AOAC PTM certification #032201 against ISO 11731:2017 for enumeration of Legionella pneumophila in sanitary and cooling tower waters.
Q: Can MICA be used to detect Legionella in cooling tower water systems?
Yes. MICA is well suited to cooling towers and other non-potable systems, such as evaporative condensers and decorative fountains. Cooling tower samples often contain high levels of background bacteria that can overgrow standard culture plates and hide Legionella colonies. MICA detects Legionella pneumophila microcolonies at 48 hours, before most competing bacteria take over. Because the entire filtered sample is analyzed, MICA can also provide a better detection limit for non-potable samples than standard culture.
That makes MICA a good fit for routine cooling tower monitoring, post-treatment verification, and investigations. Standard culture is still needed when you require serogroup identification, detection of other Legionella species, or results for compliance reporting.
Q: Can I use MICA for cooling tower Legionella testing compliance in states like New Jersey and New York?
Requirements vary by state and city, but MICA is most often used alongside compliance testing rather than in place of it. New York State requires cooling tower Legionella culture analyses to be performed by a laboratory certified through the New York State Environmental Laboratory Approval Program (ELAP), and MICA isn’t currently part of state accreditation programs. New York City added monthly culture testing for cooling towers starting May 2026 but requires counting all culturable Legionella species.
New Jersey’s Legionella law (P.L. 2024, c.66) requires cooling tower owners to keep ASHRAE 188-compliant water management programs, and standard culture remains the method of record for most compliance reporting. Within those programs, MICA can give you an earlier, culture-based look at L. pneumophila levels between required samples, after treatment, or during an investigation.
Contact Pace® to discuss how MICA can fit into your testing program and regulatory requirements.
Q: Which L. pneumophila serogroups can MICA detect?
MICA detects Legionella pneumophila across all serogroups, including serogroup 1, which causes most cases of Legionnaires’ disease. However, while MICA reports a total count of culturable L. pneumophila in CFU/mL, it does not specify which serogroups are present. When an investigation calls for serogroup identification or detection of other species, standard culture should be used alongside MICA.
Q: What percent of Legionnaires’ disease cases are caused by L. pneumophila versus other Legionella species?
There is not a definitive answer to this question, but available data suggests that Legionella pneumophila causes the vast majority of Legionnaires’ disease cases. For instance, in a widely cited international study of 508 culture-confirmed community-acquired cases, L. pneumophila accounted for about 91.5% of cases, and serogroup 1 alone accounted for 84.2%. The remaining cases were caused by other species, most often L. longbeachae and L. bozemanii.¹ The share can vary by region and setting: L. longbeachae is a more common cause in Australia and New Zealand, and other serogroups and species may play a larger role in healthcare-associated cases.¹ ²
These estimates may understate the role of other serogroups and species, because the most common clinical test, the urinary antigen test, mainly detects L. pneumophila serogroup 1.² That’s why Pace® recommends pairing MICA, which detects L. pneumophila across all serogroups, with standard culture, which identifies all culturable Legionella species and serogroups.
¹ Yu VL, et al. Distribution of Legionella species and serogroups isolated by culture in patients with sporadic community-acquired legionellosis. J Infect Dis. 2002;185:259–261.
² Vicente D, et al. Fatal case of nosocomial Legionella pneumophila pneumonia, Spain, 2018. Emerg Infect Dis. 2019;25(11).
Q: How much does MICA testing cost?
Pricing depends on your project, including sample volume, sample types, and whether MICA is paired with standard culture or other tests. Because MICA provides culture-based results in about three business days, it can help reduce the time systems stay offline during remediation or an investigation. Contact Pace® for MICA Legionella testing pricing.
Getting started with MICA testing
The right approach depends on the question being asked. Routine monitoring, remediation verification, and a suspected case or outbreak investigation may each call for a different combination of conventional culture, qPCR, MICA, or other tools. To discuss whether MICA fits your Legionella testing program, sampling requirements, or regulatory needs, contact the Pace Building Sciences team.